Posted by asghar ali on April 06, 19103 at 13:04:22:
In Reply to: Re: electrical circuit diagrams posted by peter on October 16, 19102 at 06:32:29:
: : please send me any electrical diagram based on 415& 240 v
: sewerage pump control
:
: a. A sewerage pump consists of 2 three phase 10kw pumps connected so that each pump will operate on alternate pumping cycles.
: b. the level control consists of three float switches which closes when the liquid rises above their relative position
: c. the low level float switch is set so that it operates when the liquid level rises above the level setting.
: d. the high level float switch is operated when the liquid level rises above the high level position.
: e. the extra high level float switch is set above the high level float switch and operates when the liquid reaches an unsafe level.
: f. when the high level float switch is operated the pump will start. The pump will continue to run until the liquid level falls below the low level float switch.
: g. if the liquid level keeps rising after the pump is started and the extra high level switch is operated then the second pump is started.
: h. if the liquid is not lowered to the level of the high level float switch in a period of 5 minutes an alarm will sound and a warning lamp activated.
: i. the second pump is to stop when the liquid falls below the high level float switch.
: j. this sequence of operation will continue alternating on each cycle between PUMP 1 and PUMP 2